If the diesel generator oil filter is not maintained in a timely manner during the use of the diesel generator set, the filter element will be blocked, the oil pressure will increase, the safety valve will open, and the lubricating oil will directly flow into the main oil passage, which will exacerbate the wear of the lubricating surface and affect the service life of the diesel generator set. Therefore, the oil filter should be cleaned once every 180-200 hours of operation. If any damage is found, it should be replaced immediately to prevent impurities from entering the lubrication surface. When using diesel generator sets for seasonal changes, the crankcase and various lubrication surfaces should also be cleaned. The method is to mix engine oil, kerosene, and diesel to make washing oil. After the engine oil is drained, washing oil can be added for cleaning. Then, the diesel generator should run at low speed for 3-5 minutes, drain the washing oil, and add new engine oil.
During the installation of diesel generator air filters, sealing gaskets and rubber connecting pipes should not be missed, reversed, or incorrectly installed, and the tightness of each embedded part should be ensured. The paper dust collector air filter used should be cleaned of dust once every 50-100 hours of operation. The surface dust can be brushed off with a soft bristled brush. If the working time exceeds 500 hours or it is damaged, it should be replaced in a timely manner. Use an oil bath air filter. After every 100-200 hours of operation, clean the filter element with clean diesel and replace the oil inside. If the filter element is broken, it needs to be replaced immediately. Pay attention to adding oil according to regulations during use.
The various fuel filters in the diesel generator fuel supply system should be cleaned of debris once every 100-200 hours of operation, and the fuel tank and various oil pipelines should be thoroughly cleaned. When cleaning the filter element and seals, special care should be taken and any damage should be replaced promptly. When changing oil during seasonal transitions, all components of the entire fuel supply system should be cleaned. The diesel used should meet seasonal requirements and undergo 48 hours of precipitation purification treatment.
Guangzhou Saiwei Energy Technology Co., Ltd. is a comprehensive enterprise specializing in design, production, and generator installation. Guangzhou Saiwei has many years of experience in engineering design and installation services. For many years, Guangzhou Saiwei has been committed to providing every customer with comprehensive products and energy solutions, including technical consulting, whole machine and generator supply, operation training, etc., with leading technology and first-class quality. The product range covers land diesel generator sets, marine generator sets, high-voltage generator sets, etc., and is widely used in industries such as power, communication, iron towers, healthcare, financial systems, data centers, etc. Welcome to inquire: 13302262088